General specifications | |
---|---|
Switching function | Normally open (NO) |
Output type | PNP |
Rated operating distance | 4 mm |
Installation | flush |
Output polarity | DC |
Assured operating distance | 0 ... 3.24 mm |
Reduction factor rAl | 0.4 |
Reduction factor rCu | 0.45 |
Reduction factor r304 | 0.8 |
Reduction factor rBrass | 0.55 |
Nominal ratings | |
Operating voltage | 10 ... 30 V |
Switching frequency | 0 ... 1400 Hz |
Hysteresis | typ. 5% |
Reverse polarity protection | reverse polarity protected |
Short-circuit protection | pulsing |
Voltage drop | ? 2.5 V |
Rated insulation voltage | 60 V |
Operating current | 0 ... 250 mA |
Off-state current | 0 ... 0.01 mA typ. 0.1 µA at 25 °C |
No-load supply current | ? 15 mA |
Switching state indicator | LED, yellow |
Approvals and certificates | |
Protection class | II |
UL approval | cULus Listed, General Purpose |
CSA approval | cCSAus Listed, General Purpose |
Ambient conditions | |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Mechanical specifications | |
Connection type | M8 x 1 connector, 3-pin |
Housing material | PA |
Sensing face | PA |
Degree of protection | IP67 |
Tightening torque, fastening screws | Threading M3 max: 1.1 Nm |
8 (029) 555-8-000 | |
8 (044) 555-8-000 | |
8 (017) 255-8-000 |