Описание оборудования | |
|---|---|
| KE4 switch cabinet module 8 safety-related electronic outputs, each switchable with a standard output, 8 standard inputs | |
General specifications | |
| Slave type | A/B slave, 2 standard slaves for inputs/outputs, additional slaves can be configured |
| AS-Interface specification | V3.0 |
| Required master specification | ? V3.0 |
Indicators/operating means | |
| LED FAULT | error display; LED red red: communication error |
| LED AS-i | AS-Interface voltage; LED green |
| LED AUX | ext. auxiliary voltage UAUX ; LED green |
| LED IN | switching state (input); 8 LED yellow |
| LED OUT | Switching state (output); 8 LED yellow |
| LED ALARM | Alarm signal from the control; yellow LED |
Electrical specifications | |
| Auxiliary voltage (input) | 24 V (20 VDC ... 30 VDC) PELV Max. current consumption: 8A |
| Rated operating voltage | 18,0 ... 31.6 V from AS-Interface |
| Rated operating current | < 200 mA |
Interface 1 | |
| Interface type | Chip card slot |
Input | |
| Number/Type | 8 digital inputs |
| Supply | from external auxiliary voltage UAUX |
| Voltage | 24 V DC |
| Switching threshold | U < 5V (low) U > 15V (high) |
Output | |
| Number/Type | 8 safe electronic outputs 1 - 8 release circuits |
| Supply | from external auxiliary voltage UAUX |
| Current loading capacity | 2 A per output, 8 A total Note derating |
Directive conformity | |
| Electromagnetic compatibility | |
| Machinery Directive | |
Standard conformity | |
| Degree of protection | EN60529:2000 |
| Electrical safety | EN13849-1:2008/AC:2009 |
| Climatic conditions | EN 61131-2:2007 |
| AS-Interface | EN62026-2:2013 |
| Functional safety | EN61508:2010 EN62061:2005/A1:2013 |
Programming instructions | |
| Profile | Diagnostic slave: S-7.A.E, ID1 = 5 Input/output slave: S-7.F.E, ID1 = F Configuration slave: S-7.A.5, ID1 = 7 |
Ambient conditions | |
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Altitude | 0 ... 2000 m |
Mechanical specifications | |
| Degree of protection | IP20 |
| Connection | removable terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25mm2...2.5mm2 for multiple-wire connection with two wires of equal cross-section: flexible with twin wire-end ferrules: 0.5mm2...1.5mm2 |
| Material | |
| Mass | 270 g |
| Mounting | DIN mounting rail |